Wire & Cable

AWG Wire Size Chart

Diameter, area and resistance for every gauge, calculated from the AWG definition rather than transcribed. Includes maximum runs for a 5% impedance rule on speaker wire.

AWG is a formula, not a table: each step down multiplies diameter by 92^(1/39). Three gauge steps ≈ half the area; six steps ≈ half the diameter. 12 AWG copper is 1.588 Ω per 1000 ft.

AWG wire diameter, cross-sectional area and DC resistance for copper and aluminum
4/00.46000 in / mm211600107.2190.04900.08040.0596
3/00.40964 in / mm16780685.0290.06180.10130.0752
2/00.36480 in / mm13307767.4310.07790.12780.0948
1/00.32486 in / mm10553553.4750.09830.16110.1195
10.28930 in / mm8369342.4080.12390.20310.1507
20.25763 in / mm6637133.6310.15630.25620.1900
30.22942 in / mm5263526.6710.19700.32300.2396
40.20431 in / mm4174121.1510.24850.40730.3022
50.18194 in / mm3310216.7730.31330.51360.3810
60.16202 in / mm2625113.3020.39510.64760.4805
70.14429 in / mm2081810.5490.49820.81670.6058
80.12849 in / mm165108.3660.62821.02980.7640
90.11442 in / mm130936.6340.79211.29860.9633
100.10190 in / mm103835.2610.99881.63751.2147
110.09074 in / mm82344.1721.25952.06481.5318
120.08081 in / mm65303.3091.58822.60361.9315
130.07196 in / mm51792.6242.00273.28312.4356
140.06408 in / mm41072.0812.52544.14003.0712
150.05707 in / mm32571.6503.18445.22043.8727
160.05082 in / mm25831.3094.01556.58284.8834
170.04526 in / mm20481.0385.06348.30076.1579
180.04030 in / mm16240.8236.384910.46707.7650
190.03589 in / mm12880.6538.051213.19879.7914
200.03196 in / mm10220.51810.152416.643212.3468
210.02846 in / mm8100.41012.801920.986815.5690
220.02535 in / mm6420.32616.142926.463819.6322
230.02257 in / mm5100.25820.355833.370224.7557
240.02010 in / mm4040.20525.668242.079131.2164
250.01790 in / mm3200.16232.367053.060839.3631
260.01594 in / mm2540.12940.814066.908449.6360
270.01420 in / mm2020.10251.465584.369962.5898
280.01264 in / mm1600.08164.8968106.388578.9243
290.01126 in / mm1270.06481.8334134.153499.5217
300.01003 in / mm1010.051103.1900169.1644125.4945
310.00893 in / mm800.040130.1202213.3123158.2457
320.00795 in / mm630.032164.0786268.9819199.5441
330.00708 in / mm500.025206.8992339.1799251.6205
340.00630 in / mm400.020260.8951427.6979317.2876
350.00561 in / mm320.016328.9827539.3171400.0923
360.00500 in / mm250.013414.8395680.0663504.5070
370.00445 in / mm200.010523.1029857.5478636.1716
380.00397 in / mm160.008659.62061081.3478802.1976
390.00353 in / mm130.006831.76631363.55441011.5525
400.00314 in / mm100.0051048.83791719.41041275.5442

Resistance at 20°C unless noted. Sizes 4/0 through 40 AWG — the 30s are signal and electronics gauges.

No ampacity on this page — on purpose. Current-carrying capacity is set by NEC (NFPA 70) Table 310.16 plus local amendments, and depends on insulation type, bundling, ambient temperature and the code edition your jurisdiction adopted. NFPA publishes a free read-only edition; use that and your local code rather than any number reprinted out of context.

The definition

d(n) = 0.005 × 92^((36 − n) / 39)   inch
area (cmil) = (d in mils)²
R = ρ × L / A     ρ_Cu = 1.7241×10⁻⁸ Ω·m (100% IACS), ρ_Al = 2.8264×10⁻⁸ Ω·m (61% IACS), at 20°C

Gauge numbers run backwards — 4/0 is the largest, 30 among the smallest — because the number originally counted drawing passes, not size.

Speaker wire: the 5% rule

For audio, the usual criterion is keeping wire resistance under 5% of the speaker's impedance, so damping factor stays intact. That is an impedance-matching judgment, not a safety rule, so it is independent of electrical code:

Halve those lengths for 4 Ω speakers.

Voltage drop

L_max = (V × %drop/100) / (2 × I × R_per_ft)

The factor of 2 is the return conductor — a mistake worth avoiding, since forgetting it makes every run look twice as good as it is.

Take the table with you — CSV · JSON

Data source and method

Diameter
Computed from the AWG definition above.
Resistivity
Annealed copper at 100% IACS (ASTM B3 / IEC 60028) and 1350-H19 aluminum at 61% IACS (ASTM B230). ASTM B258 defines the AWG diameters and areas, not resistivity.
Verification
Diameter and circular-mil area checked against six published gauges (4/0, 1/0, 10, 12, 14, 20); maximum deviation 0.15%. Resistance checked separately against the same six: 4/0 = 0.04901, 1/0 = 0.09827, 12 AWG = 1.588 Ω per 1000 ft, all within 0.03%.
Deliberately absent
Ampacity. See the notice above.
Not code
Voltage-drop figures are engineering calculations. Wiring must follow local code and be done by a licensed electrician.